Pinellas Coastal · Field Reference

Florida Psychrometrics

Read the house. Then read the coil.

1 · Outside the house
Moisture
— gr/lb
Dew point
— °F
Wet bulb
— °F
Total heat
— Btu/lb
2 · Inside the house
Moisture
— gr/lb
Dew point
— °F
Wet bulb
— °F
Total heat
— Btu/lb

Read in the middle of the house, away from a register, a door, and the kitchen. Give the meter two full minutes to settle before you write anything down.

3 · What the house is doing
—GRAINS HELD OUT
Moisture the
house and system
are keeping out
Inside — Held out Outside — gr/lb
4 · What a leak is costing
Extra load
— Btu/h
Of your capacity
— tons
Latent share
— Btu/h
Water carried in
— pints/day

A blower-door number is better than a guess. Without one: a tight newer house runs roughly 50–100 CFM of natural infiltration, an average older Florida block house 150–300, and a house with attic duct leaks or an unbalanced return can run far higher.

5 · Will it sweat?
Margin to dew point
— °F
Inside dew point
— °F

Shoot the supply plenum, a register face, the line set where it enters, an exterior wall behind furniture, and the slab in a closet. Anything at or below the indoor dew point is making water right now.

6 · Go look at these
Where the numbers should land
Inside conditiongr/lbDew pt
75°F / 45% — dry, well controlled5852
75°F / 50% — target6555
75°F / 55% — acceptable7158
75°F / 60% — mold threshold7860
78°F / 65% — failing9365
Clearwater design day, outside15379

Sustained indoor RH above 60% is the line where mold growth becomes likely on interior surfaces. It is a building condition, not a comfort preference.

Design stations
StationCool DB 0.4%MCWBDP 0.4%gr/lb

St. Petersburg – Clearwater is the documented station and carries the values used across the compendium. The rest are reference grade — confirm against ASHRAE Fundamentals Ch. 14 before they go on a submitted load calculation.